MAMO POWER supply qualified and intelligent ac load banks , which are widely used for mission critical environments. These load banks are ideal for applications in manufacturing, technology, transportation, hospitals, schools, public utilities, and the national military. Cooperating with government projects, we could proudly serve many valued projects from small load bank to powerful customized load bank, including programmable load bank, electronic load bank, resistive load bank, portable load bank, generator load bank, ups load bank.  Whichever load bank for rent or custom-built load bank, we could offer you competitive low pricing, all the related products or options you need, and expert sales and application assistance.


SPECS

Product Detail

Product Tags

SPECIFICATION
Rated voltage/frequency AC400-415V/50Hz/60Hz
Maximum load power Resistive load 400kW
load grades Resistive load: divided into 11 grades:
AC400V/50Hz  1, 2, 2, 5, 10, 10, 20, 50, 100, 100, 200kW
When the input voltage is lower than the rated voltage, the gear power of the load cabinet changes according to Ohm’s law.
Power Factor 1
Load accuracy (gear) ±3%
Load accuracy (whole machine) ±5%
Three-phase unbalance ≤3%;
Display accuracy Display accuracy level 0.5
control power External AC three-phase five-wire (A/B/C/N/PE) AC380V/50Hz
Communication Interface RS485、RS232;
Insulation class F
Protection class The control part meets IP54
Way of working continuously working
cooling method Forced air cooling, side inlet, side outlet

FUNCTION:

1.Control mode selection

Control the load by selecting local and intelligent methods.

2.Local control

Through the switches and meters on the local control panel, the manual loading/unloading control of the load box and the viewing of test data are performed.

3.Intelligent control

Control the load through the data management software on the computer, realize automatic loading, display, record and manage the test data, generate various curves and charts, and support printing.

4.Control mode interlocking

The system is equipped with a control mode selection switch. After selecting any control mode, the operations carried out by the other modes are invalid to avoid conflicts caused by multiple operations.

5.One-button loading and unloading

whether manual switch or software control is used, the power value can be set first, and then the total loading switch is activated, and the load will be loaded according to the preset value, so as to avoid the load caused by the power adjustment process. fluctuation.

6.Local instrument display data

The three-phase voltage, three-phase current, active power, reactive power, apparent power, power factor, frequency and other parameters can be displayed through the local measuring instrument.